4
Indoor unit
Outdoor unit
B
A
More than
30cm
More than
30cm
More than
70cm
Sunroof
Fence or
obstacles
H
600600
Top view
(unit: mm)
Front view
Front
Inspection hole
(600X600)
Control box
1000
More than
90cm
More than 90cm
More than 120cm
More than 90cm
More than
90cm
Fence or
obstacles
Fence orFence or
obstaclesobstacles
Fence or
obstacles
1. Selection of the best location
1) Indoor unit
Select location
Install the air conditioner in the location that
satisfies the following conditions.
The place shall easily bear a load
exceeding four times the indoor unit’s
weight.
The place shall be able to inspect the unit
as the figure.
• The place where the unit shall be leveled.
The place shall allow easy water
drainage.(Suitable dimension “H” is
necessary to get a slope to drain as figure.)
The place shall easily connect with the
outdoor unit.
The place where the unit is not affected by
an electrical noise.
The place where air circulation in the room
will be good .
There should not be any heat source or
steam near the unit
2) Outdoor unit
If an awning is built over the unit to prevent
direct sunlight or rain exposure, be careful
that heat radiation from the condenser is
not restricted.
There should not be any animals or plants
which could be affected by hot air
discharged.
Ensure the spaces indicated by arrows
from the wall, ceiling, fence or other
obstacles.
Following descriptions are for the Top Discharge
Type outdoor unit.
• 120Cm clearance required on top of unit.
60Cm clearance required between units for proper airflow.
One side must be 90Cm for service.
Two of the remaining three sides may be 30Cm.
3) Piping length and the elevation
2. Installation of Indoor, Outdoor Unit
• If 18K Model is installed at a distance of 15m,
188g of refrigerant should be added (15-7.5) x 25g = 188g
• Capacity is based on standard length and maximun allowance length is on the basis of reliability.
18K BTU/h(50Hz)
5/8" 1/4" 7.5 50 5 30 25
H/P 5/8" 1/4" 7.5 50 5 30 30
C/O 5/8" 1/4" 7.5 50 5 30 25
48K BTU/h 3/4'' 3/8" 7.5 50 5 30 50
3/4" 1/2" 7.5 50 5 30 100
Capacity
Gas Liquid
Elevation B(m)
Length A(m)
* Additional
refrigerant
(g/m)
Pipe Size
(Diameter: Ø)
Standard
Standard
Max.
Max.
60K BTU/h
(LB-E6082CL)
24K
BTU/h