1. Selection of the best location
1) Indoor unit
Select location
Install the air conditioner in the location that
satisfies the following conditions.
• The place shall easily bear a load
exceeding four times the indoor unit’s
weight.
• The place shall be able to inspect the unit
as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water
drainage.(Suitable dimension “H” is
necessary to get a slope to drain as figure.)
• The place shall easily connect with the
outdoor unit.
• The place where the unit is not affected by
an electrical noise.
• The place where air circulation in the room
will be good .
• There should not be any heat source or
steam near the unit
2) Outdoor unit
• If an awning is built over the unit to prevent
direct sunlight or rain exposure, be careful
that heat radiation from the condenser is
not restricted.
• There should not be any animals or plants
which could be affected by hot air
discharged.
• Ensure the spaces indicated by arrows
from the wall, ceiling, fence or other
obstacles.
Following descriptions are for the Top Discharge
Type outdoor unit.
• 120Cm clearance required on top of unit.
•
60Cm clearance required between units for proper airflow.
✽
One side must be 90Cm for service.
Two of the remaining three sides may be 30Cm.
3) Piping length and the elevation
2. Installation of Indoor, Outdoor Unit
• If 18K Model is installed at a distance of 15m,
188g of refrigerant should be added (15-7.5) x 25g = 188g
• Capacity is based on standard length and maximun allowance length is on the basis of reliability.
18K BTU/h(50Hz)
5/8" 1/4" 7.5 50 5 30 25
H/P 5/8" 1/4" 7.5 50 5 30 30
C/O 5/8" 1/4" 7.5 50 5 30 25
48K BTU/h 3/4'' 3/8" 7.5 50 5 30 50
3/4" 1/2" 7.5 50 5 30 100
Capacity
Gas Liquid
Elevation B(m)
Length A(m)
* Additional
refrigerant
(g/m)
Pipe Size
(Diameter: Ø)
Standard
Standard
Max.
Max.
60K BTU/h
(LB-E6082CL)
24K
BTU/h