LGAir ConditionerINSTALLATION MANUALLGType : Wall Mountedhttp://www.lgservice.comIMPORTANT• Please read this instruction manual completely before inst
InstallationInstallation Manual 10Piping Length and Elevation9k Ø9.52 3/8 Ø 6.35 1/4 7.5 10 2 15 20 Pipe SizeCapacity(Btu/h)GAS L
Indoor unitThe wall you select should be strong and solidenough to prevent vibration1. Mount the installation plate on the wall with type "A"
Installation Flaring WorkMain cause for gas leakage is due to defect of flaring work. Carry out correct flaring work in thefollowing procedure.Cut th
InstallationCheck1. Compare the ared work with the gure by.2. If a ared section is defective, cut it o anddo aring work again.1.Pull the screw ca
InstallationInstallation Information. For right piping. Follow the instruction below.Good case• Press on the tubing cover and unfold the tubing to do
InstallationInstallation of Indoor Unit1. Hook the indoor unit onto the upper portion ofthe installation plate.( engage the three hooksat the top of t
Installation3. Tape the tubing pipe, drain hose and the connection cable. Be sure that the drain hose is locatedat the lowest side of the bundle. Loca
InstallationWrap the insulation material around theconnecting portion.1. Overlap the connection pipe insulationmaterial and the indoor unit pipe insul
1. Align the center of the pipings and sufficientlytighten the flare nut by hand.2. Finally, tighten the flare nut with torquewrench until the wrench
InstallationIndoor unitConnect the cable to the indoor unit by connecting the wires to the terminals on the control boardindividually according to the
2 Air conditonerAir Conditioner Installation ManualCONTENTSSafety Precautions...3Introduction ...
InstallationOutdoor unit1. Connect the wires to the terminals on thecontrol board individually.2. Secure the cable onto the control board withthe cord
Installation Checking the DrainageTo check the drainage.1. Pour a glass of water on the evaporator.2. Ensure the water flows through the drainhose o
InstallationForming the PipingForm the piping by wrapping theconnecting portion of the indoor unitwith insulation material and secure itwith two kinds
Installation Air PurgingThe air and moisture remaining in the refrigerant system have undesirable effects as indicated below.1. Pressure in the syst
InstallationSoap water method1. Remove the caps from the 2-way and 3-way valves.2. Remove the service-port cap from the 3-way valve.3. Apply a soap wa
Installation 1. Check that all tubing and wiring are properly connected.2. Check that the gas and liquid side service valves are fully open.• Ration
InstallationIf the actual pressure is higher than shown, the system is most likely over-charged, and chargeshould be removed. If the actual pressure a
InstallationInstallation guide at the seaside1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas,
P/No.: MFL62106406 After reading this manual, keep it in a place easily accessible to the user forfuture reference.
IQVWDOODWLRQ0DQXDO 3Safety Precautions To prevent the injury of the user or other people and property damage, the following instructionsmust be foll
Safety Precautions Do not install the product at a place wherethere is concern of falling down.• Otherwise, it may result in personal injury.Use cau
,QVWDOODWLRQ0DQXDO 5Safety Precautions InstallationInstall the drain hose to ensure that draincan be securely done.• Otherwise, it may cause wate
The gure of product can be dierent according to the type of model.Introduction This symbol alerts you to the risk of electric shock.This symbol al
Type "A" screwType "C" screwType "B" screwThe feature can be changed according a type of model.Remote control holderInst
InstallationInstallation MapBase PlateAir Outlet VentsAir Inlet VentsVinyl tape (Wide)• Apply after carrying out a drainage test.• To carry out the
Select the best Location More than 15cm.More than5cm.More than 2.3m.More than5cm.Install the indoor unit on the wall where the height from the floor i